142

THERMAL SPECIFICATIONS

The thermal specifications of the radiators are presented in accordance with the PN-EN 442-2 standard in the form of normal output (∆T = 50K temp. 75/65/20/°C) and the exponents of the average difference of “n” temperatures included in the technical data tables. Outputs other than those given in the table can be calculated using the formulas presented below, or by means of a simplified method with the use of conversion factors (see table opposite).

Radiator output at any temperature set:

Radiator output recalculating for given temperature levels

DATA:

Radiator model: AST-50/120

Normal output for ∆T = 50K (75/65/20 °C): 883 W Heating system temperature parameters: Feed water temperature tz = 85°C Return water temperature tp = 60°C Ambient temperature to = 25°C

“n” exponent from the technical data table: n = 1,2958

CALCULATIONS:

F

n - normal output (value included in technical data table) ∆T - average temperature difference ∆T

n = 50K - average temperature difference for normal conditions (75/65/20 °C)

n - average temperature difference exponent (value included in technical data table) t

z - feed water temperature t

p - return water temperature t o - ambient temperature

F = F

n

[ ] n

∆T ∆T

n

∆T = - t o

2

t

z + t

p

where

EXAMPLE USE OF FORMULAS

∆T = - t o = - 25 = 47,5

2

t

z + t

p 85 + 60

2

F = F

n

[ ] n

= 883

[ ] 1,2958

826 W

∆T ∆T

n

47,5 50

Page 142 - IP Katalog PRO 2012 Ver. 2.00